Abstract :
The condition of the insulation system frequently limits the useful life of the windings of a rotating machine. This is a function of thermal, electrical, environmental, and mechanical factors plus the type of duty to which the machine is subjected. The thermal classifications of the variety of insulating materials that make up an applied insulation system are presented. Strand and turn insulation, common groundwall insulation systems, armor tapes and coatings, side packing and wedging methods, are discussed. Four factors that influence insulation life are identified: thermal, electrical, ambient (environmental), and mechanical plus performance (intended) and duty (mode of operation). Finally, accelerated aging tests, inspections and diagnostic test during service outages, and online monitoring of partial discharges are discussed.<>
Keywords :
electric machines; insulation testing; life testing; machine insulation; machine testing; monitoring; partial discharges; stators; accelerated aging tests; armor tapes; armour coatings; common groundwall insulation; diagnostic test; insulating materials; insulation life; insulation system; large rotating machines; online monitoring; partial discharges; service outages; side packing; stator windings; strand insulation; thermal classifications; turn insulation; wedging methods; Accelerated aging; Coatings; Condition monitoring; Insulation life; Machine windings; Mechanical factors; Rotating machines; Stator windings; Testing; Thermal factors;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/57.223893
Filename :
223893
Link To Document :
بازگشت