Title :
A technique for estimating transmission line fault locations from digital impedance relay measurements
Author :
Sachdev, M.S. ; Agarwal, R.
Author_Institution :
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask., Canada
fDate :
1/1/1988 12:00:00 AM
Abstract :
A technique is presented that is suitable for estimating locations of shunt faults. The estimates are reasonably accurate even if the fault resistance is substantial and the transmission line is connected to energy sources at both terminals. The technique uses post fault fundamental-frequency voltages and currents measured at the two line terminals. The measurements need not be synchronized, and the source impedances are not used by the estimation procedure. The mathematical development of the technique is presented. Sample test results using simulated fault data are included.
Keywords :
electric impedance measurement; fault location; power system protection; power transmission lines; relay protection; digital impedance relay measurements; energy sources; fault resistance; post fault fundamental-frequency voltages; post-fault fundamental-frequency currents; shunt faults; transmission line fault locations; Current measurement; Digital relays; Electrical resistance measurement; Fault currents; Fault location; Frequency; Impedance measurement; Power system relaying; Power transmission lines; Testing; Transmission line measurements; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on