• DocumentCode
    932475
  • Title

    Vacuum breakdown with microsecond delay time [interrupters]

  • Author

    Anders, S. ; Jüttner, B. ; Lindmayer, M. ; Rusteberg, C. ; Pursch, H. ; Unger-Weber, F.

  • Author_Institution
    Berlin Dept., Inst. of Plasma Phys., Germany
  • Volume
    28
  • Issue
    4
  • fYear
    1993
  • fDate
    8/1/1993 12:00:00 AM
  • Firstpage
    461
  • Lastpage
    467
  • Abstract
    The delay time of voltage breakdown has been analyzed as a function of the time interval to preceding interruption of high currents. With intervals >1 ms the behavior of the gap corresponded to cold electrodes. For this case, in a separate experiment, the dependence of the delay time on various parameters has been studied. At constant voltage a steep increased with the gap distance was found. This leads to the conclusion that field emission rather than a clump process is responsible for late breakdowns
  • Keywords
    circuit breakers; electric breakdown; electron field emission; vacuum insulation; cold electrodes; constant voltage; field emission; gap distance; microsecond delay time; voltage breakdown; Delay effects; Dielectric breakdown; Electric breakdown; Electrodes; Electron emission; Interrupters; Physics; Plasma transport processes; Vacuum breakdown; Voltage;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.231526
  • Filename
    231526