    Mechanical shocks as cause of late discharges in vacuum circuit breakers

  • Author

    Gebel, R. ; Hartmann, W.

  • Author_Institution
    Siemens AG Corp. Res. & Dev., Erlangen, Germany
  • Volume
    28
  • Issue
    4
  • fYear
    1993
  • fDate
    8/1/1993 12:00:00 AM
  • Firstpage
    468
  • Lastpage
    472
  • Abstract
    The time dependence of late discharges in high-voltage vacuum circuit breakers after current interruption has been measured as a function of the mechanical and electrical stress exerted on the vacuum circuit breaker bottle. A correlation between the occurrence of strong, shocklike acceleration peaks of >104 m/s2 and the increase of the probability of late discharges has been found. A reduction of the shock wave amplitudes by simple mechanical damping results in a reduction of the probability of late strikes by as much as 50%. It is concluded that most of the late discharges observed in these experiments are caused by particles which adhere loosely to the contact and vapor shield surfaces, and which are released by the strong mechanical shocks
  • Keywords
    circuit breakers; circuit-breaking arcs; damping; shock waves; contact surfaces; current interruption; electrical stress; late discharges; mechanical damping; mechanical stress; probability; shock wave amplitudes; shocklike acceleration peaks; time dependence; vacuum circuit breakers; vapor shield surfaces; Acceleration; Circuit breakers; Current measurement; Damping; Electric shock; Electric variables measurement; Mechanical variables measurement; Shock waves; Stress measurement; Time measurement;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.231527
  • Filename
    231527