• DocumentCode
    934524
  • Title

    Subsynchronous resonance of a power station with two identical generating units

  • Author

    Jennings, G.D. ; Harley, R.G. ; Levy, D.C.

  • Author_Institution
    University of Natal, Department of Electrical Engineering, Durban, South Africa
  • Volume
    133
  • Issue
    1
  • fYear
    1986
  • fDate
    1/1/1986 12:00:00 AM
  • Firstpage
    33
  • Lastpage
    43
  • Abstract
    The paper investigates the effect of adding a second 1072 MVA turbogenerator to an existing one in a power station feeding a series capacitor compensated transmission line. In carrying out the investigation, the new two-generator system is modelled as one equivalent generator with increased capacity, and also as a multimachine system with two separate generators. A comparison of these models shows that, for this type of stability study and this transmission system configuration, there is no advantage gained in modelling the two generators separately rather than as one equivalent generator. The results further show that conditions can exist where the system is stable with one generator but unstable with two, and vice versa.
  • Keywords
    power stations; power transmission lines; resonance; turbogenerators; 1072 MVA turbogenerator; 1400 km transmission line; power station; series capacitor compensated transmission line; stability;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1986.0006
  • Filename