DocumentCode :
934675
Title :
Differential protection of muIti-ended circuits
Author :
Gray, C.B. ; Singh, P.N.P.
Author_Institution :
University of Bradford, School of Electrical and Electronic Engineering, Bradford, UK
Volume :
133
Issue :
1
fYear :
1986
fDate :
1/1/1986 12:00:00 AM
Firstpage :
59
Lastpage :
66
Abstract :
Representative power system networks incorporating multi-terminal feeders are analysed under typical pre-fault load conditions, to establish suitability for differential protection on the basis of a circular relay characteristic of marginal operation expressed on a complex plane in terms of the ratio of local current to the sum of remote currents in the steady state. Differential protection is shown to be feasible, with discrimination improved at lower levels of protective circuit energisation by expanding the radius of the area of stability on the complex plane inversely as the magnitude of the equivalent remote relaying quantity. The desired effect is demonstrated practically in an analogue realisation using ideal signalling, by the modification of a two-input mean amplitude comparator relay through the provision of additional restraint with 1 cycle operating time achievable.
Keywords :
power system protection; relay protection; amplitude comparator relay; differential protection; multi-ended circuits; multiterminal feeders; power system networks; power system protection; protective circuit energisation; signalling;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C
Publisher :
iet
ISSN :
0143-7046
Type :
jour
DOI :
10.1049/ip-c.1986.0010
Filename :
4646727
Link To Document :