• DocumentCode
    934675
  • Title

    Differential protection of muIti-ended circuits

  • Author

    Gray, C.B. ; Singh, P.N.P.

  • Author_Institution
    University of Bradford, School of Electrical and Electronic Engineering, Bradford, UK
  • Volume
    133
  • Issue
    1
  • fYear
    1986
  • fDate
    1/1/1986 12:00:00 AM
  • Firstpage
    59
  • Lastpage
    66
  • Abstract
    Representative power system networks incorporating multi-terminal feeders are analysed under typical pre-fault load conditions, to establish suitability for differential protection on the basis of a circular relay characteristic of marginal operation expressed on a complex plane in terms of the ratio of local current to the sum of remote currents in the steady state. Differential protection is shown to be feasible, with discrimination improved at lower levels of protective circuit energisation by expanding the radius of the area of stability on the complex plane inversely as the magnitude of the equivalent remote relaying quantity. The desired effect is demonstrated practically in an analogue realisation using ideal signalling, by the modification of a two-input mean amplitude comparator relay through the provision of additional restraint with 1 cycle operating time achievable.
  • Keywords
    power system protection; relay protection; amplitude comparator relay; differential protection; multi-ended circuits; multiterminal feeders; power system networks; power system protection; protective circuit energisation; signalling;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1986.0010
  • Filename