Title :
Quantification of corona discharges on nonceramic insulators
Author :
Pinnangudi, B. ; Gorur, R.S. ; Kroese, A.J.
Author_Institution :
Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ, USA
fDate :
6/1/2005 12:00:00 AM
Abstract :
This paper attempts to establish a correlation of the visual images of corona obtained from a camera with discharge magnitude measured with conventional partial discharge equipment. A linear relationship is shown between the transformed image parameters and the discharge magnitude, thereby providing a means for quantifying corona observations made during routine maintenance inspections, of insulators from ground. Different insulator designs using silicone rubber (SIR) and ethylene propylene diene monomer (EPDM) housings were examined. The effect of fog has been examined by performing experiments inside a fog chamber. It is shown that this information can be used along with the corona degradation characteristics of housing materials to identify discharge patterns that can pose problems to the integrity of the insulator.
Keywords :
corona; ethylene-propylene rubber; image processing; inspection; silicone rubber insulators; EPDM; camera; corona discharges; discharge magnitude measurement; ethylene propylene diene monomer; field inspection; image processing; maintenance inspections; nonceramic insulators; partial discharge; silicone rubber insulators; visual images; Cameras; Corona; Degradation; Dielectrics and electrical insulation; Electric variables measurement; Fault location; Hardware; Inspection; Moisture; Partial discharges;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2005.1453456