DocumentCode
938664
Title
Fault location in transmission lines using one-terminal postfault voltage data
Author
De Morais Pereira, Carlos Eduardo ; Zanetta, L.C.
Author_Institution
Escola Politecnica, Univ. de Sao Paulo, Brazil
Volume
19
Issue
2
fYear
2004
fDate
4/1/2004 12:00:00 AM
Firstpage
570
Lastpage
575
Abstract
A new algorithm for fault location in transmission lines, with fault distance calculation based on steady-state measured phasors in local terminal is presented. For the postfault, only voltage phasors are required, avoiding possible errors due to current transformer saturation; the current phasors are required only in prefault time, when saturation does not occur. The algorithm does not use simplifying hypothesis but requires system equivalent data at both line terminals and the fault classification, considering fault resistance purely resistive. In order to verify the algorithm performance, a parametric analysis of variables that influences short-circuit conditions is developed, including an analysis of remote equivalent setting. The results show that the algorithm is very accurate, even in cases when the remote equivalent is not well fitted.
Keywords
current transformers; distance measurement; fault location; power transmission faults; power transmission lines; voltage measurement; EHV transmission lines; current phasors; current transformer saturation; distance measurement; fault classification; fault diagnosis; fault distance calculation; fault location; fault resistance; postfault voltage data; steady state phasors; Admittance; Algorithm design and analysis; Fault location; Impedance; Performance analysis; Transmission line matrix methods; Transmission line measurements; Transmission line theory; Transmission lines; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.824391
Filename
1278411
Link To Document