Impact of difference of feeder impedances on the performance of a static transfer switch
Author :
Mokhtari, Hossein ; Iravani, M. Reza
Author_Institution :
Dept. of Electr. Eng., Sharif Univ. of Technol., Tehran, Iran
Volume :
19
Issue :
2
fYear :
2004
fDate :
4/1/2004 12:00:00 AM
Firstpage :
679
Lastpage :
685
Abstract :
Conventionally, control system of a static transfer switch (STS) is designed based on the assumption that the STS terminal voltages are in-phase. This paper investigates the impact of phase difference of the STS terminal voltages on the STS transfer time and cross current. The phase difference is assumed to be a result of the difference of the feeder impedances. The paper shows that phase differences of even up to 4.5°, which are accompanied by up to 5% voltage drop at the STS terminal, can noticeably increase the transfer time and the cross current magnitude. The studies are conducted on the IEEE STS-l benchmark system using the PSCAD/EMTDC software.
Keywords :
control system synthesis; electric impedance; power engineering computing; power supply quality; switchgear; IEEE STS-I benchmark system; control system; cross current magnitude; feeder impedance; load transfer; phase difference; power quality; sensitive loads; static transfer switch; terminal voltages; transfer time; Control systems; EMTDC; Impedance; Logic; PSCAD; Phase detection; Sociotechnical systems; Switches; Thyristors; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.825125
Filename :
1278426
Link To Document :
بازگشت