Abstract :
The paper deals with compensation of frequently time-variable loads by means of STATCOM controllers. An arc furnace is considered as a heavily distributing load. The STATCOM system was used to ensure good power quality at the point of common coupling. For analysis of the system performance, the PSCAD/EMTDC programme was applied. Simulation models of the load and two types of STATCOM controllers, 12-pulse and 24-pulse, are discussed in the paper. A PSCAD model of a measurement block is also proposed for power quality assessment. Some results of simulation are presented, which show the compensation effectiveness.
Keywords :
EMTP; arc furnaces; controllers; power supply quality; power system simulation; static VAr compensators; PSCAD/EMTDC programme; STATCOM controller; arc furnace; frequently time-variable loads; power quality; shunt compensation;