• DocumentCode
    949274
  • Title

    A three-phase line-interactive UPS system implementation with series-parallel active power-line conditioning capabilities

  • Author

    Silva, Sérgio Augusto Oliveira da ; Donoso-Garcia, Pedro Francisco ; Cortizo, Porfirio Cabaleiro ; Seixas, Paulo Fernando

  • Author_Institution
    Dept. of Electr. Eng., Fed. Center of Technol. Educ., Cornelio Procopio, Brazil
  • Volume
    38
  • Issue
    6
  • fYear
    2002
  • Firstpage
    1581
  • Lastpage
    1590
  • Abstract
    This paper presents a three-phase line-interactive uninterruptible power supply (UPS) system with series-parallel active power-line conditioning capabilities, using a synchronous-reference-frame (SRF)-based controller, which allows an effective power-factor correction, load harmonic current suppression, and output voltage regulation. The three-phase UPS system is composed of two active power filter topologies. The first one is a series active power filter, which works as a sinusoidal current source in phase with the input voltage. The other is a parallel active power filter, which works as a sinusoidal voltage source in phase with the input voltage, providing to the load a regulated and sinusoidal voltage with low total harmonic distortion. Operation of a three-phase phase-locked loop structure, used in the proposed line-interactive UPS implementation, is presented and experimentally verified under distorted utility conditions. The control algorithm using the SRF method and the active power flow through the UPS system are described and analytically studied. Design procedures, digital simulations, and experimental results for a prototype are presented to verify the good performance of the proposed three-phase line-interactive UPS system.
  • Keywords
    active filters; harmonic distortion; power conversion harmonics; power harmonic filters; uninterruptible power supplies; active power flow; line-interactive UPS implementation; load harmonic current suppression; output voltage regulation; parallel active power filter; power-factor correction; series active power filter; series-parallel active power-line conditioning; sinusoidal current source; sinusoidal voltage source; synchronous reference frame-based controller; three-phase line-interactive uninterruptible power supply; three-phase phase-locked loop structure; total harmonic distortion; Active filters; Control systems; Low voltage; Phase locked loops; Power harmonic filters; Power system harmonics; Topology; Total harmonic distortion; Uninterruptible power systems; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2002.804760
  • Filename
    1058113