DocumentCode
950604
Title
Location of the prebreakdown region in a cross-linked polyethylene insulated cable
Author
Naybour, R.D.
Author_Institution
EA Technol., Capenhurst, UK
Volume
140
Issue
5
fYear
1993
fDate
9/1/1993 12:00:00 AM
Firstpage
363
Lastpage
367
Abstract
A method of locating discharges during breakdown tests on medium-voltage cables is described. The resistive screen of the cable attenuates the discharge pulses and the location is made by using the magnitude of the pulses recorded at each end of the cable, allowance must be made for pulse reflection. Tests on an 11 kV polyethylene insulated cable that contained large vented water trees are used to illustrate the method. Total discharge energy and location were recorded for a single discharging site. The test was stopped prior to breakdown and a volume of insulation containing a single electrical tree was cut from the cable. The computed discharge energy was compared with the eroded volume within the electrical tree.
Keywords
cable insulation; dielectric measurement; electric breakdown of solids; insulation testing; polymers; 11 kV; breakdown tests; cross-linked polyethylene insulated cable; discharge energy; discharges; electrical tree; eroded volume; medium-voltage cables; prebreakdown region; pulse reflection; resistive screen; vented water trees;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings A
Publisher
iet
ISSN
0960-7641
Type
jour
Filename
234750