Abstract :
Two-phase liquid immersion cooling of computers is becoming an increasingly favorable heat removal strategy. A re-entrant cavity heat sink has been developed to address these needs. In confined situations, the vapor generated moves through the channel formed between adjacent substrates. Bubble transport is therefore affected by the channel width. Saturated pool boiling results are presented and discussed for vertically oriented channels of widths ranging from 0.1 cm to 0.6 cm to cover typical values likely to be encountered. The heat source was a deposited aluminum thin film heater of size 0.9 cm by 0.9 cm. The cavities were laid out over a 2.5 cm by 2.5 cm area. Testing was carried out in FC-72, It was found that the presence of a parallel plate affected the heat transfer performance adversely
Keywords :
boiling; bubbles; channel flow; cooling; heat sinks; integrated circuit packaging; two-phase flow; 0.1 to 0.6 cm; Al thin film heater; FC-72; Si wafer; bubble transport; channel width; heat removal strategy; heat transfer performance; microconfigured heat sink; microelectronics cooling; reentrant cavity heat sink; saturated pool boiling; two-phase liquid immersion cooling; vertically oriented channels; Cooling; Heat engines; Heat sinks; Heat transfer; Microelectronics; Silicon; Space heating; Substrates; Thermal conductivity; Viscosity;
fLanguage :
English
Journal_Title :
Components, Packaging, and Manufacturing Technology, Part A, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9886
Type :
jour
DOI :
10.1109/95.465149
Filename :
465149
Link To Document :
بازگشت