DocumentCode :
956809
Title :
Adaptive out-of-step relaying using phasor measurement techniques
Author :
Centeno, Virgilio ; De La Ree, J. ; Phadke, A.G. ; Michel, G. ; Murphy, J. ; Burnett, R.
Author_Institution :
Virginia Polytech. Inst. & State Univ., Blacksburg, VA, USA
Volume :
6
Issue :
4
fYear :
1993
Firstpage :
12
Lastpage :
17
Abstract :
Adaptive relaying proposes to provide protection functions that will adapt to changing power system conditions. The adaptive out-of-step relay presented recognizes power system changes and uses a modified system impedance matrix to change relay settings. An investigation of a Florida-Georgia 500 kV interconnection initially, used a simple two-machine mode to represent the interconnection. After this approach is tested a three-machine Florida model will be constructed. The results from the two approaches will then be compared. The configuration used to implement the relay consists of two or more phasor measurement units (PMUs), which provide synchronized real-time information regarding the state of the system. These PMUs are discussed and data provided by the PMUs is analyzed.<>
Keywords :
adaptive control; matrix algebra; power system computer control; power system interconnection; power system measurement; power system protection; real-time systems; relay protection; 500 kV; adaptive out-of-step relay; impedance matrix; interconnection; phasor measurement; power system; protection; real-time; Impedance; Measurement techniques; Phasor measurement units; Power system interconnection; Power system measurements; Power system modeling; Power system protection; Power system relaying; Protective relaying; Relays;
fLanguage :
English
Journal_Title :
Computer Applications in Power, IEEE
Publisher :
ieee
ISSN :
0895-0156
Type :
jour
DOI :
10.1109/67.238199
Filename :
238199
Link To Document :
بازگشت