DocumentCode :
957923
Title :
Nonlinear VAr control for damping multivariable swing equations
Author :
Pierre, Donald A.
Author_Institution :
Dept. of Electr. Eng., Montana State Univ., Bozeman, MT, USA
Volume :
3
Issue :
3
fYear :
1988
fDate :
8/1/1988 12:00:00 AM
Firstpage :
1033
Lastpage :
1038
Abstract :
Idealized swing equations are used in the development of local control strategies for VAr (reactive volt-ampere) units, with the objective of providing damping to all oscillatory modes of multimachine power systems. A one-machine infinite-bus system is used to introduce and motivate the method. The control strategy provides damping even during severe transients involving reverse power swings. For systems containing n machines, simulation results indicate that n -1 locally controlled VAr units, using only local output feedback, can be placed to dampen all oscillatory modes of the system, provided that a stable equilibrium point exists and that the initial disturbance is limited in severity
Keywords :
damping; power control; power systems; idealized swing equations; multimachine power systems; multivariable swing equations; nonlinear VAr control; Control systems; Damping; Nonlinear equations; Power system control; Power system interconnection; Power system simulation; Power system transients; Power systems; Reactive power; Voltage control;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.14558
Filename :
14558
Link To Document :