DocumentCode
963911
Title
Development of current limiting arcing horn for prevention of lightning faults on distribution lines
Author
Washino, Masami ; Fukuyama, Atsushi ; Kit, Kuniji ; Kat, Kazuaki
Author_Institution
Chubu Electr. Power Co. Inc., Nagoya, Japan
Volume
3
Issue
1
fYear
1988
fDate
1/1/1988 12:00:00 AM
Firstpage
187
Lastpage
196
Abstract
Wire breakage by arc fusion due to lightning flashovers has become a serious problem in Japan as a result of the widespread use of insulated wires as distribution lines. To solve this problem, a current-limiting arcing horn that has a nonlinear resistor element of zinc oxide has been developed. With this element the power follow current is interrupted and conductor arc fusion is prevented. Even in the case of bare wires, this device effectively prevents power-supply service interruptions. The design and performance of the device and its ability to prevent lightning faults on actual distribution lines are described
Keywords
arcs (electric); distribution networks; insulators; lightning protection; power system protection; Japan; ZnO; arc fusion; bare wires; current limiting arcing horn; distribution lines; insulated wires; lightning faults prevention; nonlinear resistor element; power-supply service interruptions; wire breakage; Cable insulation; Circuit faults; Conductors; Current limiters; Flashover; Lightning; Power supplies; Resistors; Voltage; Wires; Zinc oxide;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.4245
Filename
4245