• DocumentCode
    965808
  • Title

    Harmonic losses in a three phase transformer core

  • Author

    Basak, A. ; Moses, A.J.

  • Author_Institution
    IEEE TMAG
  • Volume
    14
  • Issue
    5
  • fYear
    1978
  • fDate
    9/1/1978 12:00:00 AM
  • Firstpage
    990
  • Lastpage
    992
  • Abstract
    The iron loss of laminated cores is always greater than the nominal loss of the steel as measured in an Epstein Square or single strip tester. The extra loss is due to a number of factors. Flux harmonics have been measured locally in individual laminations of grain-oriented silicon-iron in a 3 phase transformer core and the loss associated with the harmonic components has been estimated. For the experimental core used, the loss associated with the harmonics in the yokes and limbs was 15% of the total loss, and corner loss accounted for 17% of the total. The calculated loss in the core accounted for over 80% of the measured loss, the difference being due to the effect of mechanical stress and also the errors in estimating the losses.
  • Keywords
    Magnetic core losses; Power transformers; Iron; Lamination; Loss measurement; Phase estimation; Phase measurement; Phase transformers; Steel; Strips; Testing; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.1978.1059779
  • Filename
    1059779