• DocumentCode
    966860
  • Title

    Ultrasaturation Phenomenon in Power Transformers—Myths and Reality

  • Author

    Wiszniewski, Andrzej ; Rebizant, Waldemar ; Bejmert, Daniel ; Schiel, Ludwig

  • Author_Institution
    Wroclaw Univ. of Technol., Warsaw
  • Volume
    23
  • Issue
    3
  • fYear
    2008
  • fDate
    7/1/2008 12:00:00 AM
  • Firstpage
    1327
  • Lastpage
    1334
  • Abstract
    In this paper, the ultrasaturation phenomenon of power transformers during their energization is studied. It is shown that under special conditions, the currents observed after transformer switching on do not contain enough restraining information (e.g., second harmonic), which may lead to protection maloperation. This paper concentrates on a thorough explanation of the problem and possible causes of ultrasaturation. Theoretical investigations are supported and illustrated with simulation studies performed both with MATLAB and electromagnetic transients program-alternative transients program. The outcomes of this research can further be used as hints for substation operation personnel as well as for the development of new protection stabilization criteria, which is not discussed further in this paper.
  • Keywords
    EMTP; power system harmonics; power system transients; power transformer protection; MATLAB; electromagnetic transients program-alternative transients program; harmonic restraint; power transformers; protection maloperation; protection stabilization criteria; transformer protection; transformer switching; transient analysis; ultrasaturation phenomenon; Harmonic restraint; transformer protection; transient analysis; ultrasaturation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.909211
  • Filename
    4378286