• DocumentCode
    967878
  • Title

    Transient Analysis of Parameters Governing Grounding Systems by the FDTD Method

  • Author

    Tuma, Eduardo T. ; Dos Santos, Ronaldo O. ; De Oliveira, Rodrigo M S ; da Silva Souza, C.L.

  • Volume
    4
  • Issue
    1
  • fYear
    2006
  • fDate
    3/1/2006 12:00:00 AM
  • Firstpage
    55
  • Lastpage
    61
  • Abstract
    The main purpose of this work is to analyze the transient behavior of grounding systems parameters by the development of a parallel computational code based on the Finite Difference Time Domain Method (FDTD-3D). The obtained results for potential, current and Transitory Grounding Resistance (TGR), considering a single electrode, strongly agree with real measurements available in literature. Additional results have been obtained through the implementation of several grounding configurations, including stratified soils. Such results and the flexible presented methodology can be used to project systems able to provide higher levels of protection from lightning discharges or failures on the main electrical power system.
  • Keywords
    FDTD method; grounding resistance; lightning protection; parallel processing; stratified soil; transient analysis; Concurrent computing; Current measurement; Electrical resistance measurement; Electrodes; Finite difference methods; Grounding; Power system protection; Power system transients; Time domain analysis; Transient analysis; FDTD method; grounding resistance; lightning protection; parallel processing; stratified soil; transient analysis;
  • fLanguage
    English
  • Journal_Title
    Latin America Transactions, IEEE (Revista IEEE America Latina)
  • Publisher
    ieee
  • ISSN
    1548-0992
  • Type

    jour

  • DOI
    10.1109/TLA.2006.1642450
  • Filename
    1642450