• DocumentCode
    968816
  • Title

    State estimation of a boiler model using the unscented Kalman filter

  • Author

    Lo, Kwok L. ; Rathamarit, Y.

  • Author_Institution
    Univ. of Strathclyde, Glasgow
  • Volume
    2
  • Issue
    6
  • fYear
    2008
  • fDate
    11/1/2008 12:00:00 AM
  • Firstpage
    917
  • Lastpage
    931
  • Abstract
    The state estimation of a 300 MW drum-type boiler is examined, using an unscented Kalman filter to improve estimation accuracy by preserving the nonlinearities of the boiler equations. The boiler is modelled by a system of differential state equations for the dynamics of the circulation loop and another set of partial differential equations for the heat exchangers such as the superheaters, reheater and economiser. These modelling equations are the results of first principle balance equations, which have a form that is unsuitable for the extended Kalman filter method because of errors between the linear and nonlinear propagation of the boiler states and the difficulties in obtaining the Jacobian of the state model for the propagation of model uncertainties. An unscented Kalman filter is used to circumvent this problem as it treats the system model as a black box. Filtering results from simulated plant data are presented to demonstrate the effectiveness of the filter application.
  • Keywords
    Kalman filters; boilers; partial differential equations; power filters; power system state estimation; steam power stations; Jacobian; boiler model; nonlinear propagation; partial differential equations; power 300 MW; principle balance equations; state estimation; superheaters; unscented Kalman filter;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd:20080217
  • Filename
    4663101