Author :
Hui, D. ; Wang, Z.K. ; Zhang, J.Y. ; Zhang, D. ; Dai, S.T. ; Zhao, C.H. ; Zhu, Z.Q. ; Li, H.D. ; Zhang, Z.F. ; Guan, Y. ; Xiao, L.Y. ; Lin, L.Z. ; Li, L.F. ; Gong, L.H. ; Xu, X.D. ; Lu, J.Z. ; Fang, Z. ; Zhang, H.X. ; Zeng, J.P. ; Li, G.P. ; Zhou, S.Z.
Abstract :
Superconducting Fault Current Limiter (SFCL) is an attractive appliance for modern electrical power system. A 10.5kV/1.5 kA three-phase HTS fault current limiter was developed by IEE, CAS. This improved rectifier-type SFCL with HTS coil of 6.25 mH is going on a demonstrated long-term reliable operation in a real 10.5 kV substation located in Hunan, China. In a three-phase-to-ground short circuit test of grid, the prospective fault current of 3.5 kA was limited to 635 A at the pre-setup short-circuit point successfully
Keywords :
fault current limiters; high-temperature superconductors; power grids; power system faults; rectifiers; short-circuit currents; substations; superconducting coils; superconducting device testing; 1.5 kA; 10.5 kV; 3.5 kA; China; HTS coil; HTS fault current limiter; Hunan; electrical power system; fault current; power grid; rectifier-type SFCL; substation; three-phase-to-ground short circuit test; Circuit testing; Content addressable storage; Fault current limiters; High temperature superconductors; Home appliances; Power system faults; Power system reliability; Substations; Superconducting coils; Superconducting transmission lines; HTS coil; short circuit test; superconducting fault current limiter;