Abstract :
The use of adjustable-speed drives requires transformers capable of withstanding high levels of harmonic currents under normal operating conditions. Experience has been that overheating problems are much more common with dry-type transformers than with liquid-filled transformers. Transformer insulation life is determined by the hot spot temperature but confirmation of hot spot temperature rise is one performance characteristic which is ignored in industry standards. This is especially important for transformers rated for nonsinusoidal load currents. The design of transformers for nonsinusoidal load currents should include an analysis of the eddy loss distribution in the windings and calculation of the hot spot temperature rise. Calculations and thermal tests giving only average winding temperature rises are not sufficient. Thermal tests with nonsinusoidal currents and measurements of hot spot temperature rises are extremely difficult on large transformers. The combination of testing and analysis may be the only economically practical approach. Analysis indicates that the dry type transformer hot spot temperature is very sensitive to the eddy loss magnitude and distribution. The Underwriters Laboratories Inc. (UL) K-factor rated dry type transformer and the recommended practices given in ANSI/IEEE C57.110 are reviewed. When purchasing transformers subject to nonsinusoidal load currents, considerations should be given to the manufacturer´s development program and capability to calculate the eddy loss distribution and hot spot temperatures
Keywords :
ANSI standards; IEEE standards; eddy current losses; eddy currents; power transformer insulation; power transformers; thermal analysis; transformer oil; ANSI/IEEE C57.110 recommended practices; K-factor rated dry type transformer; Underwriters Laboratories; adjustable-speed drives; dry-type transformers; eddy loss distribution; hot spot temperature rise; liquid-filled transformers; nonsinusoidal load currents; overheating; thermal tests; transformer design; transformer insulation life; transformer windings; Current measurement; Electrical equipment industry; Insulation life; Laboratories; Manufacturing; Power transformer insulation; Temperature distribution; Temperature sensors; Testing; Variable speed drives;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.502176
Filename :
502176
Link To Document :
بازگشت