• DocumentCode
    973732
  • Title

    Hybrid Active Filter for Reactive and Harmonics Compensation in a Distribution Network

  • Author

    Corasaniti, V.F. ; Barbieri, M.B. ; Arnera, P.L. ; Valla, M.I.

  • Author_Institution
    Inst. de Investig. Tecnol. para Redes y Equipos Electricos-Laboratorios de Alta Tension, Univ. Nac. de La Plata, La Plata
  • Volume
    56
  • Issue
    3
  • fYear
    2009
  • fDate
    3/1/2009 12:00:00 AM
  • Firstpage
    670
  • Lastpage
    677
  • Abstract
    The problem of reactive power and harmonics in the medium voltage level of a power distribution system is considered in this paper. Reconfiguration of the power delivery network imposes new constraints in a distribution substation so that the reactive compensation should be increased. The alternative of a shunt hybrid active filter connected to the 13.8-kV level to enhance the power quality is analyzed in this paper. This proposal uses the existing capacitor bank to build a hybrid filter in which the complementary compensation is performed by the active filter. The performance of the hybrid filter is evaluated with extensive simulations considering reactive power, harmonics, and unbalance compensation. It shows very good behavior in steady-state and transient conditions.
  • Keywords
    active filters; distribution networks; harmonic distortion; power harmonic filters; power system harmonics; power system transients; reactive power; substations; capacitor bank; distribution substation; harmonic compensation; power delivery network; power distribution network; power quality enhancement; reactive power compensation; shunt hybrid active filter; steady-state condition; transient condition; voltage 13.8 kV; Active filters; harmonic distortion; power distribution; power quality; reactive power;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/TIE.2008.2007997
  • Filename
    4663839