DocumentCode :
975050
Title :
Loss-of-mains detection for small generators
Author :
Hopewell, P.D. ; Jenkins, N. ; Cross, A.D.
Volume :
143
Issue :
3
fYear :
1996
fDate :
5/1/1996 12:00:00 AM
Firstpage :
225
Lastpage :
230
Abstract :
A new loss-of-mains detection method for use with very small generators is proposed. A known load is repeatedly switched on to the supply, and the resulting voltage changes used to estimate the source impedance, and hence to detect loss of mains. Correlating the load switching with the voltage change prevents false operation arising from random load changes. Experiments and simulations are discussed which demonstrate the principles of the technique. Test results are presented which show that the technique operates correctly, and can reliably detect a loss of mains without being susceptible to false tripping
Keywords :
electric generators; electric impedance measurement; load (electric); machine testing; machine theory; small electric machines; switching; false tripping; load switching; loss-of-mains detection; simulations; small generators; source impedance measurement; testing; voltage change;
fLanguage :
English
Journal_Title :
Electric Power Applications, IEE Proceedings -
Publisher :
iet
ISSN :
1350-2352
Type :
jour
DOI :
10.1049/ip-epa:19960286
Filename :
502359