DocumentCode
975050
Title
Loss-of-mains detection for small generators
Author
Hopewell, P.D. ; Jenkins, N. ; Cross, A.D.
Volume
143
Issue
3
fYear
1996
fDate
5/1/1996 12:00:00 AM
Firstpage
225
Lastpage
230
Abstract
A new loss-of-mains detection method for use with very small generators is proposed. A known load is repeatedly switched on to the supply, and the resulting voltage changes used to estimate the source impedance, and hence to detect loss of mains. Correlating the load switching with the voltage change prevents false operation arising from random load changes. Experiments and simulations are discussed which demonstrate the principles of the technique. Test results are presented which show that the technique operates correctly, and can reliably detect a loss of mains without being susceptible to false tripping
Keywords
electric generators; electric impedance measurement; load (electric); machine testing; machine theory; small electric machines; switching; false tripping; load switching; loss-of-mains detection; simulations; small generators; source impedance measurement; testing; voltage change;
fLanguage
English
Journal_Title
Electric Power Applications, IEE Proceedings -
Publisher
iet
ISSN
1350-2352
Type
jour
DOI
10.1049/ip-epa:19960286