• DocumentCode
    975050
  • Title

    Loss-of-mains detection for small generators

  • Author

    Hopewell, P.D. ; Jenkins, N. ; Cross, A.D.

  • Volume
    143
  • Issue
    3
  • fYear
    1996
  • fDate
    5/1/1996 12:00:00 AM
  • Firstpage
    225
  • Lastpage
    230
  • Abstract
    A new loss-of-mains detection method for use with very small generators is proposed. A known load is repeatedly switched on to the supply, and the resulting voltage changes used to estimate the source impedance, and hence to detect loss of mains. Correlating the load switching with the voltage change prevents false operation arising from random load changes. Experiments and simulations are discussed which demonstrate the principles of the technique. Test results are presented which show that the technique operates correctly, and can reliably detect a loss of mains without being susceptible to false tripping
  • Keywords
    electric generators; electric impedance measurement; load (electric); machine testing; machine theory; small electric machines; switching; false tripping; load switching; loss-of-mains detection; simulations; small generators; source impedance measurement; testing; voltage change;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2352
  • Type

    jour

  • DOI
    10.1049/ip-epa:19960286
  • Filename