DocumentCode :
975266
Title :
Partial discharge. XVIII. Errors in the location of partial discharges in high voltage solid dielectric cables
Author :
Kreuger, F.H. ; Wezelenburg, M.G. ; Wiemer, A.G. ; Sonneveld, W.A.
Author_Institution :
High Voltage Lab., Delft Univ. of Technol., Netherlands
Volume :
9
Issue :
6
fYear :
1993
Firstpage :
15
Lastpage :
22
Abstract :
Errors in partial discharge (PD) location on high voltage dielectric cables caused by both mechanical and electrical phenomena are discussed. The sources of error relevant to PD location include errors in measuring time delays, scatter caused by noise and disturbances, pulse propagation distortion, errors in cable length measurement, and trivial errors in experimental technique. Experiments to determine typical PD location error were carried out using a detector with a 10 MHz bandwidth. Extensive tests were carried out on a 200 m, 15 kV cable with metering marks on the outer sheath, as well as a 590 m, 10 kV cable without metering marks.<>
Keywords :
cable insulation; cable testing; charge measurement; insulation testing; measurement errors; partial discharges; position measurement; power cables; 10 MHz; 10 kV; 15 kV; 200 m; 590 m; cable length measurement; electrical phenomena; high voltage solid dielectric cables; mechanical phenomena; metering marks; outer sheath; partial discharge location errors; pulse propagation distortion; scatter; tests; time delay measurement errors; Dielectric measurements; Distortion measurement; Length measurement; Mechanical cables; Noise measurement; Partial discharge measurement; Partial discharges; Pulse measurements; Solids; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/57.245980
Filename :
245980