DocumentCode
975519
Title
A meter placement method for state estimation
Author
Baran, Mesut E. ; Zhu, Jinxiang ; Zhu, Hongbo ; Garren, Kenneth E.
Author_Institution
Dept. of Electr. & Comput. Eng., North Carolina State Univ., Raleigh, NC, USA
Volume
10
Issue
3
fYear
1995
fDate
8/1/1995 12:00:00 AM
Firstpage
1704
Lastpage
1710
Abstract
In this paper a new meter placement method is presented. The method is comprehensive in that all the important aspects of the problem-cost, accuracy, reliability, and bad data processing capability requirements-are incorporated into the method. The problem is solved in three stages. The objective in the first stage is to place a minimum set of measurements which satisfies the desired accuracy requirements. In the second stage, additional meters are placed to incorporate reliability requirements which are defined in term of loss of RTUs. In the third stage, additional meters are placed to improve the bad data processing ability of the state estimation in terms of detecting and identifying the bad data
Keywords
observability; power system measurement; power system reliability; power system state estimation; accuracy requirements; bad data detection; bad data identification; bad data processing capability requirements; meter placement method; power systems; reliability; remote terminal units loss; state estimation; Costs; Data processing; Loss measurement; Observability; Power measurement; Power system analysis computing; Power system measurements; Power system reliability; SCADA systems; State estimation;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.466470
Filename
466470
Link To Document