• DocumentCode
    981398
  • Title

    Design of HVDC converter station equipment subject to severe seismic performance requirements

  • Author

    Enblom, R. ; Coad, J.N.O. ; Berggren, S.

  • Author_Institution
    ABB Corp. Res., Vasteras, Sweden
  • Volume
    8
  • Issue
    4
  • fYear
    1993
  • fDate
    10/1/1993 12:00:00 AM
  • Firstpage
    1766
  • Lastpage
    1772
  • Abstract
    Severe seismic design levels were specified for the upgrading of the HVDC link between the principal islands of New Zealand. A number of novel design solutions were required to fulfil the performance requirements for the electric equipment. The purpose of this paper is to give an overview of design solutions and verification methods in the light of a specification stating performance criteria rather than specific allowables. Modifications to items of high voltage electrical equipment are described that reduce the seismic loads in the equipment and enable standard equipment to be used in areas of high seismicity. The seismic performance is further improved by controlling the eventual collapse mechanism
  • Keywords
    DC power transmission; design engineering; maintenance engineering; project engineering; substations; HVDC converter station; HVDC link; New Zealand; collapse mechanism; design; performance criteria; power transmission; project engineering; seismic design; substations; upgrading; Acceleration; Damping; Frequency; Geology; HVDC transmission; Hazards; Life estimation; Lifetime estimation; Thyristors; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.248269
  • Filename