DocumentCode :
981760
Title :
Insulation recovery characteristics after fault arc interruption on UHV (1000 kV class) transmission lines
Author :
Goda, Yutaka ; Matsuda, Shoji ; Inabe, T. ; Ozaki, Yuzo
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Kanagawa, Japan
Volume :
8
Issue :
4
fYear :
1993
fDate :
10/1/1993 12:00:00 AM
Firstpage :
1907
Lastpage :
1913
Abstract :
The insulation recovery time after arc interruption must be known to select the adequate reclosing dead time of rapid auto-reclosing on transmission lines. In order to study insulation recovery characteristics after arc interruption on UHV (1000 kV class) transmission lines, many tests were carried out using the high power test facilities of CRIEPI. In this paper the authors describe the experimental results of these tests of insulation recovery characteristics after arc interruption of UHV transmission lines, and some factors influencing these characteristics
Keywords :
arcs (electric); electrical faults; high-voltage techniques; insulators; power transmission lines; 1000 kV; CRIEPI; UHV transmission lines; fault arc interruption; high power test facilities; insulation recovery characteristics; insulation recovery time; rapid auto-reclosing; reclosing dead time; Arc discharges; Assembly; Circuit breakers; Circuit testing; Insulation testing; Insulator testing; Poles and towers; Power transmission lines; Switches; Switching circuits;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.248301
Filename :
248301
Link To Document :
بازگشت