DocumentCode
983561
Title
Local band shedding
Author
Adibi, M.M. ; Thorne, D.K.
Author_Institution
IRD Corp., Bethesda, MD, USA
Volume
3
Issue
3
fYear
1988
Firstpage
1220
Lastpage
1229
Abstract
An effective local-load-shedding scheme has been developed to alleviate equipment overloads in underground transmission networks. It offers a very fast and reliable algorithm where accuracy and speed are traded, depending on the severity of overload. For overloads greatly in excess of short-time ratings, the speed of removing the overloads within the specified time is given higher priority than the accurate minimization of load curtailments. To provide positive and reliable collective action, overloads are overcorrected by shedding more loads than is absolutely necessary, since the excess loads shed can subsequently be restored by partial restoration. The local shedding scheme has been tested by simulation at the Potomac Electric Power Company for a number of single and multiple outages in the 138 kV underground transmission network with good results.<>
Keywords
load shedding; underground transmission systems; 138 kV; Potomac Electric Power Company; equipment overloads; load curtailments; local-load-shedding; short-time ratings; underground transmission networks; Combustion; Control systems; Delay; Electrical equipment industry; Load flow; Substations; Testing; Time measurement; Turbines; Voltage control;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.14585
Filename
14585