• DocumentCode
    984801
  • Title

    Computer-aided measurement of partial discharges in HV equipment

  • Author

    Gulski, E.

  • Author_Institution
    Dept. of Electr. Eng., Delft Univ. of Technol., Netherlands
  • Volume
    28
  • Issue
    6
  • fYear
    1993
  • fDate
    12/1/1993 12:00:00 AM
  • Firstpage
    969
  • Lastpage
    983
  • Abstract
    A previously developed method of partial discharge (PD) recognition is used to evaluate PD in HV devices. Using conventional discharge detection (bandwidth ~400 kHz), the PD patterns are studied. By means of unambiguous statistical operators like skewness, kurtosis, number of peaks, etc., quantitative information about the discharge source can be obtained. In the case of an unknown defect, a combination of these operators is compared to the same set of operators for a known configuration. In this way, a statement can be made on the character of a discharge source. The use of this technique in evaluating different discharges in HV cable and in 400 kV SF6 insulation confirms the usefulness of the new approach
  • Keywords
    automatic test equipment; cable testing; electric variables measurement; high-voltage techniques; insulation testing; partial discharges; pattern recognition; statistical analysis; 400 kHz; 400 kV; HV cable; HV equipment; PD measurement; PD patterns; PD recognition; SF6; SF6 insulation; computer-aided measurement; discharge source; partial discharges; statistical operators; Automatic testing; Bandwidth; Cable insulation; Dielectrics and electrical insulation; Fault location; Laboratories; Partial discharges; Pattern recognition; Shape; System testing;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.249370
  • Filename
    249370