• DocumentCode
    984809
  • Title

    PD analysis of rotating AC machines

  • Author

    Contin, A. ; Rabach, G.

  • Author_Institution
    Trieste Univ., Italy
  • Volume
    28
  • Issue
    6
  • fYear
    1993
  • fDate
    12/1/1993 12:00:00 AM
  • Firstpage
    1033
  • Lastpage
    1042
  • Abstract
    The problem of the interpretation of partial discharge (PD) measurements is approached by means of the shape analysis of PD amplitude distributions. Experimental cumulative PD distributions, detected insulation systems of HV rotating machine stator windings, are plotted on a Weibull graph in order to identify multiple PD sources. Examples of the application of PD distribution shape analysis as a diagnostic tool for AC HV stator insulation systems are presented and discussed. The calibration procedure and the significance of average parameters for degradation inference are reviewed
  • Keywords
    AC machines; calibration; high-voltage techniques; insulation testing; machine insulation; machine testing; partial discharges; stators; AC HV stator insulation systems; HV machine stator windings; PD amplitude distributions; PD analysis; Weibull graph; calibration procedure; cumulative PD distributions; diagnostic tool; electric machines; multiple PD sources; partial discharge measurements; rotating AC machines; shape analysis; AC machines; Acoustic measurements; Calibration; Degradation; Fault location; Insulation; Partial discharges; Rotating machines; Shape measurement; Stator windings;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.249371
  • Filename
    249371