• DocumentCode
    985467
  • Title

    Effect of puffer volume and operating force on dielectric recovery performance in thermal puffer-type gas circuit breaker

  • Author

    Osawa, Naoki ; Yoshioka, Yoshio

  • Author_Institution
    Dept. of Electr. Eng., Kanazawa Inst. of Technol., Ishikawa, Japan
  • Volume
    20
  • Issue
    3
  • fYear
    2005
  • fDate
    7/1/2005 12:00:00 AM
  • Firstpage
    1897
  • Lastpage
    1903
  • Abstract
    In order to investigate the influence of puffer volume VP and operating force to dielectric performance of GCB at current interruption, we calculated the prospective dielectric withstand voltage VW between arcing contacts. The withstand voltage was calculated by the electric field strength appeared on arcing contacts and the allowable electric field strength EW* of hot gas due to thermal puffer action. We could clarify that large initial puffer volume VP can increase withstand voltage VW at current breaking point and also that an optimum point exists in operating force F. For example, it was found that in case of the operating force of 1000 kgf, the puffer volume VP of 1.2 liter would be best choice in the interrupting condition of i=50 kA and arcing time of 1.35 cycle.
  • Keywords
    arcs (electric); gas blast circuit breakers; 50 kA; arcing contacts; current breaking point; current interruption; dielectric recovery performance; electric field strength; operating force; puffer volume; thermal puffer-type gas circuit breaker; Breakdown voltage; Circuit breakers; Circuit faults; Contacts; Dielectrics; Fluid flow; Power system reliability; Temperature; Thermal force; Transient analysis; Electric field analysis and gas flow analysis; gas circuit breakers; thermal puffer; withstand voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.843486
  • Filename
    1458859