DocumentCode
985467
Title
Effect of puffer volume and operating force on dielectric recovery performance in thermal puffer-type gas circuit breaker
Author
Osawa, Naoki ; Yoshioka, Yoshio
Author_Institution
Dept. of Electr. Eng., Kanazawa Inst. of Technol., Ishikawa, Japan
Volume
20
Issue
3
fYear
2005
fDate
7/1/2005 12:00:00 AM
Firstpage
1897
Lastpage
1903
Abstract
In order to investigate the influence of puffer volume VP and operating force to dielectric performance of GCB at current interruption, we calculated the prospective dielectric withstand voltage VW between arcing contacts. The withstand voltage was calculated by the electric field strength appeared on arcing contacts and the allowable electric field strength EW* of hot gas due to thermal puffer action. We could clarify that large initial puffer volume VP can increase withstand voltage VW at current breaking point and also that an optimum point exists in operating force F. For example, it was found that in case of the operating force of 1000 kgf, the puffer volume VP of 1.2 liter would be best choice in the interrupting condition of i=50 kA and arcing time of 1.35 cycle.
Keywords
arcs (electric); gas blast circuit breakers; 50 kA; arcing contacts; current breaking point; current interruption; dielectric recovery performance; electric field strength; operating force; puffer volume; thermal puffer-type gas circuit breaker; Breakdown voltage; Circuit breakers; Circuit faults; Contacts; Dielectrics; Fluid flow; Power system reliability; Temperature; Thermal force; Transient analysis; Electric field analysis and gas flow analysis; gas circuit breakers; thermal puffer; withstand voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.843486
Filename