Determination of threshold electric field EC of soil under high impulse currents
Author :
Nor, N. Mohamad ; Haddad, A. ; Griffiths, H.
Author_Institution :
Fac. of Eng., Multimedia Univ., Selangor, Malaysia
Volume :
20
Issue :
3
fYear :
2005
fDate :
7/1/2005 12:00:00 AM
Firstpage :
2108
Lastpage :
2113
Abstract :
A threshold electric-field intensity (Ec), above which soil ionization occurs, has been known to be important to predict soil behavior under high impulse currents. However, published results reveal a wide range of values of Ec (1.3 to 20 kV/cm) and the effects of many other factors such as soil resistivity, impulse polarity, and electrode geometry require further investigation. The aim of this investigation was to quantify the effects of soil resistivity, the impulse polarity on the threshold electric field (Ec) of soil under fast transients.
Keywords :
electric fields; electrical resistivity; ionisation; electrode geometry; high impulse current; impulse polarity; soil ionization; soil resistivity; threshold electric field intensity; Circuit testing; Conductivity; Earth; Electric breakdown; Electrodes; Grounding; Impulse testing; Ionization; Soil; Voltage; Impulse polarity; soil electrical properties; soil ionization; soil resistivity; threshold electric field;