• DocumentCode
    985926
  • Title

    Evaluation of grounding schemes used for maintenance of overhead distribution lines

  • Author

    Lee, Chien-Hsing ; Hsu, Teng-Chin

  • Author_Institution
    Dept. of Electr. Eng., Nat. Yunlin Univ. of Sci. & Technol., Taiwan
  • Volume
    20
  • Issue
    3
  • fYear
    2005
  • fDate
    7/1/2005 12:00:00 AM
  • Firstpage
    2211
  • Lastpage
    2218
  • Abstract
    This paper evaluates seven basic grounding schemes used for maintenance of overhead de-energized distribution lines in the system of Taiwan Power Company. The test results are summarized to determine the effective grounding scheme of protecting workers on de-energized overhead distribution lines from the source-side due to an accidental energization. The fault currents were recorded with various grounding configurations. As a result, two of grounding configurations are considered lethal.
  • Keywords
    earthing; maintenance engineering; occupational safety; power distribution lines; power overhead lines; Taiwan Power Company; fault currents; grounding schemes; maintenance; overhead deenergized distribution lines; workers protection; Conductors; Electric shock; Electrical safety; Fault currents; Grounding; Power distribution lines; Power system faults; Power system protection; Testing; Voltage; Electric shocks; re-energization; temporary grounding conductor; touch voltage;