DocumentCode
987922
Title
Dielectric behavior of GIS switching disconnectors comparison of possible phase opposition tests
Author
Lalot, J. ; Sabot, A. ; Kieffer, J.
Author_Institution
Electricite de France, Paris, France
Volume
3
Issue
1
fYear
1988
fDate
1/1/1988 12:00:00 AM
Firstpage
214
Lastpage
222
Abstract
The dielectric behavior of a GIS (gas-insulated switchgear) switching disconnector is investigated by means of full-phase opposition tests to obtain data on the discharge-to-ground phenomenon. This phenomenon, which is a function of the voltage across the disconnector switch contacts before restrike and of the amplitude of the overvoltage after restrike, displays a very large scatter. In addition, the time-to-crest of the overvoltage has a great influence on the discharge to ground. A discharge-to-ground mechanism to explain all of these features is proposed. The guarantees of same disconnector switching given by two possible phase opposition tests having different overvoltage shapes and amplitude are compared
Keywords
gaseous insulation; switchgear; GIS switching disconnectors; dielectric behavior; discharge-to-ground phenomenon; gas-insulated switchgear; overvoltage; phase opposition tests; time-to-crest; Contacts; Dielectrics; Displays; Gas insulation; Geographic Information Systems; Scattering; Switches; Switchgear; Testing; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.4248
Filename
4248