DocumentCode :
989134
Title :
Earthquake simulator testing of base-isolated power transformers
Author :
Murota, Nobuo ; Feng, Maria Q. ; Liu, Gee Yu
Author_Institution :
Dept. of Seismic Isolation Eng., Bridgestone Corp., Yokohama, Japan
Volume :
21
Issue :
3
fYear :
2006
fDate :
7/1/2006 12:00:00 AM
Firstpage :
1291
Lastpage :
1299
Abstract :
This paper presents a comprehensive study involving triaxial earthquake simulator testing on seismic isolation of electric power transformers. In this study, two isolation systems were developed: one using sliding bearings combined with rubber bearings and the other segmented high-damping rubber bearings. Triaxial earthquake simulator testing was performed using a large-scale transformer model equipped with a real bushing. The effectiveness of the base isolation system in reducing the response acceleration of power transformer systems was demonstrated. Important observations were made on the seismic responses of the transformer and bushing. In particular, the vertical component of the ground motion induced a high-frequency response of the bushing when the transformer was isolated with the sliding isolation system. This is because the vertical motion changes the friction forces in the sliding bearings that excite high modes in the transformer-bushing system. Furthermore, the effect of the interaction with the bushing connecting cables on the response of the bushing in the base-isolated system was experimentally evaluated. In conclusion, the base isolation technology, when properly designed, is a highly effective measure for seismic protection of power transformers.
Keywords :
bushings; earthquakes; frequency response; machine bearings; power transformer testing; base-isolated power transformer; bushing; earthquake simulator testing; friction forces; high-frequency response; rubber bearings; seismic isolation; seismic responses; sliding bearings; sliding isolation system; triaxial; Acceleration; Earthquakes; Friction; Insulators; Large-scale systems; Performance evaluation; Power system modeling; Power transformers; Rubber; Testing; Base isolation; bushing; earthquake simulator; electric power transformer; seismic; substations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.874586
Filename :
1645168
Link To Document :
بازگشت