Title :
Analysis of some measurement issues in bushing power factor tests in the field
Author :
Zhang, S.
Author_Institution :
PCORE Electr. Co. Inc., LeRoy, NY, USA
Volume :
21
Issue :
3
fYear :
2006
fDate :
7/1/2006 12:00:00 AM
Firstpage :
1350
Lastpage :
1356
Abstract :
The power factor measurement is widely used in the evaluation of bushing insulation conditions in the field. Some measurement issues occur in the field tests which give abnormal readings of bushing C1 and/or C2 power factors. This paper provides an engineering analysis of the possible measurement issues in the bushing field tests such as testing a bushing on a transformer or in its shipping crate, or a bushing with wet/contaminated voltage/test tap or wet/dirty porcelain surface.
Keywords :
bushings; power factor measurement; testing; bushing insulation conditions; bushing power factor tests; porcelain; power factor measurement; shipping crate; transformer; Circuit testing; Insulation testing; Insulators; Oil insulation; Pollution measurement; Power measurement; Power transformer insulation; Reactive power; Transformer cores; Windings; Bushing; crate; porcelain; power factor; test tap; transformer; voltage tap;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.874616
Filename :
1645175
Link To Document :