DocumentCode
991405
Title
Double winding, high-Voltage cable wound Generator: steady-State and fault analysis
Author
Touma-Holmberg, Marguerite ; Srivastava, Kailash
Author_Institution
ALSTOM Power, Vasteras, Sweden
Volume
19
Issue
2
fYear
2004
fDate
6/1/2004 12:00:00 AM
Firstpage
245
Lastpage
250
Abstract
This paper describes a detailed circuit representation of synchronous machines equipped with two similar or dissimilar armature windings. The equivalent circuit at steady state is presented. The self and mutual leakage inductances of the two sets of three-phase stator windings are evaluated by the finite element method as well as an analytical method. The simulation results from a steady-state analysis as well as a fault analysis are verified experimentally on the world´s first high-voltage generator Powerformer installed in Porjus, Sweden, rated at 45 kV and 11 MVA.
Keywords
electrical faults; failure analysis; finite element analysis; inductance; stators; synchronous generators; armature windings; cable wound generator; fault analysis; finite element method; leakage inductance; steady-state analysis; synchronous machines; three-phase stator windings; voltage generator Power-former; Analytical models; Circuit faults; Circuit simulation; Equivalent circuits; Finite element methods; Machine windings; Stator windings; Steady-state; Synchronous machines; Wounds; Double winding; Powerformer; fault; inductance; leakage; steady state; synchronous;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.2004.827024
Filename
1300686
Link To Document