• DocumentCode
    993552
  • Title

    A new algorithm for evaluating the fields associated with HVDC power transmission lines in the presence of Corona and strong wind

  • Author

    Yu, Ming ; Kuffel, E.

  • Author_Institution
    Dept. of Electr. Eng., Manitoba Univ., Winnipeg, Man., Canada
  • Volume
    29
  • Issue
    2
  • fYear
    1993
  • fDate
    3/1/1993 12:00:00 AM
  • Firstpage
    1985
  • Lastpage
    1988
  • Abstract
    A novel algorithm for calculating high-voltage direct-current (HVDC) fields in the presence of corona and strong winds based on the boundary element-method (BEM) is presented. The algorithm uses an auxiliary Poisson´s equation for updating the space-charge density during the iteration. The iteration process is convergent for wind velocities tested up to 12-m/s. The algorithm can be used for the calculation of ionized fields associated with bipolar HVDC power transmission lines, with some modifications
  • Keywords
    corona; electromagnetic fields; power overhead lines; wind; Corona; HVDC fields; HVDC power transmission lines; auxiliary Poisson´s equation; bipolar transmission; boundary element-method; ionized fields; iteration process; space-charge density; strong wind; wind velocities; Conductors; Corona; HVDC transmission; Ionization; Nonlinear equations; Poisson equations; Power generation; Power transmission lines; Space charge; Voltage;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/20.250798
  • Filename
    250798