DocumentCode
993552
Title
A new algorithm for evaluating the fields associated with HVDC power transmission lines in the presence of Corona and strong wind
Author
Yu, Ming ; Kuffel, E.
Author_Institution
Dept. of Electr. Eng., Manitoba Univ., Winnipeg, Man., Canada
Volume
29
Issue
2
fYear
1993
fDate
3/1/1993 12:00:00 AM
Firstpage
1985
Lastpage
1988
Abstract
A novel algorithm for calculating high-voltage direct-current (HVDC) fields in the presence of corona and strong winds based on the boundary element-method (BEM) is presented. The algorithm uses an auxiliary Poisson´s equation for updating the space-charge density during the iteration. The iteration process is convergent for wind velocities tested up to 12-m/s. The algorithm can be used for the calculation of ionized fields associated with bipolar HVDC power transmission lines, with some modifications
Keywords
corona; electromagnetic fields; power overhead lines; wind; Corona; HVDC fields; HVDC power transmission lines; auxiliary Poisson´s equation; bipolar transmission; boundary element-method; ionized fields; iteration process; space-charge density; strong wind; wind velocities; Conductors; Corona; HVDC transmission; Ionization; Nonlinear equations; Poisson equations; Power generation; Power transmission lines; Space charge; Voltage;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/20.250798
Filename
250798
Link To Document