• DocumentCode
    996691
  • Title

    Losses in Transformers for Use With Mercury Arc Rectifiers

  • Author

    DeBlieux, E.V.

  • Author_Institution
    General Trans. Engg. Dept., General Electric Co., Pittsfield, Mass.
  • Volume
    50
  • Issue
    3
  • fYear
    1931
  • Firstpage
    999
  • Lastpage
    1005
  • Abstract
    This paper developes the mathematical formulas and discusses the assumption involved in the methods for determining the losses of transformers for use with mercury arc rectifiers. The methods discussed have been proposed for the A. I. E. E. Standards. From test readings of current taken under service conditions, a rigid calculation of copper losses is made. From this calcutlation it is shown that the proposed methods give values that are accurate within satisfactory limits. The paper also presents the advantages of the proposed methods for determining the losses of transformers for use with mercury arc rectifiers.
  • Keywords
    Arc discharges; Circuit testing; Coils; Current supplies; Frequency; Rectifiers; Transformers;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1931.5055907
  • Filename
    5055907