Title :
Preventive maintenance system with a different gas injecting facility for GIS
Author :
Utsumi, T. ; Endo, F. ; Ishikawa, T. ; Iwaasa, S. ; Yamagiwa, T.
Author_Institution :
Hitachi Ltd., Japan
fDate :
7/1/1993 12:00:00 AM
Abstract :
A preventive maintenance system for gas insulated switchgear (GIS) is developed. It detects signs of trouble and prevents breakdowns in service. The system constantly monitors UHF signals, which are generated by partial discharges (PDs), and propagate in the GIS, by using couplers built into the apparatus. The PDs are detected at high sensitivity (5 pC) and located according to the attenuation of the signals. Then the system injects a different gas into the section where PDs are occurring and improves the dielectric strength. This prevents faults in service and allows remedial actions to be taken with less accuracy. By injecting a small quantity (5-10%) of c-C/sub 4/F/sub 8/ into the GIS, dielectric strength is raised more than 20%. A preventive maintenance system with a facility to inject a different gas is constructed for a full-scale GIS model. The system detects and locates PDs, and automatically injects the different gas to improve the dielectric strength.<>
Keywords :
electric breakdown of gases; electric strength; gaseous insulation; maintenance engineering; partial discharges; sulphur compounds; switchgear; GIS; SF/sub 6/; UHF signals; c-C/sub 4/F/sub 8/; dielectric strength; electric breakdown; gas injecting facility; gas insulated switchgear; partial discharges; preventive maintenance; sensitivity; Couplers; Dielectric breakdown; Electric breakdown; Gas insulation; Geographic Information Systems; Partial discharges; Preventive maintenance; Signal generators; Switchgear; UHF propagation;
Journal_Title :
Power Delivery, IEEE Transactions on