Dynamic system monitoring (DSM) for HVDC modulation control
Author
Grund, Carl E. ; Sweezy, George ; Hauer, John F. ; Balser, S.J. ; Nilsson, Stig
Author_Institution
GE Ind. & Power Syst., Schenectady, NY, USA
Volume
8
Issue
3
fYear
1993
fDate
7/1/1993 12:00:00 AM
Firstpage
853
Lastpage
860
Abstract
As part of an advanced power modulation control system for HVDC lines, dynamic system monitors (DSMs) were installed at the DC terminals of the Square Butte system. The monitors are used to validate the computer models used for the controller design and to validate the performance of the controllers after installation. The use of Prony analysis and Fourier techniques to analyze system disturbances and to validate the computer models is described. Excellent results are achieved for some well-defined disturbances.<>
Keywords
DC power transmission; modulation; monitoring; power system control; power system measurement; power transmission lines; Fourier techniques; HVDC; Prony analysis; USA; design; disturbances; dynamic system monitors; performance; power modulation control system; power system measurement; power transmission lines;