Title :
Measurement of the post arc current of HV circuit breakers: application to short circuit tests with ITRV
Author :
Guilloux, C. ; Therme, Y. ; Scarpa, P.G.
Author_Institution :
High Power Test Lab., EDF Les Renardieres, France
fDate :
7/1/1993 12:00:00 AM
Abstract :
Power test laboratories and manufacturers use facilities for measuring the post-arc current in SF/sub 6/ circuit breakers. Such measurements have been improved to produce further comparison with modeling. Calculations based on experimentation on two circuit breakers, one having a high post-arc current level, the other not having a detectable post-arc current, permit comparison of three test circuits. It is concluded that the international standard, in specifying stresses and not circuits, does not lead to notable differences in the severity of the tests.<>
Keywords :
circuit breakers; circuit-breaking arcs; gaseous insulation; power system measurement; short-circuit currents; standards; sulphur compounds; switchgear testing; SF/sub 6/ circuit breakers; international standard; post arc current; power system measurement; short circuit tests; stresses; switchgear testing; test circuits;
Journal_Title :
Power Delivery, IEEE Transactions on