DocumentCode
998454
Title
Breakdown of Glass with Alternating Potentials
Author
Kenney, N.D. ; Luery, A.M. ; Moriaty, J.D.
Author_Institution
Massachusetts Institute of Technology.
Volume
51
Issue
2
fYear
1932
fDate
6/1/1932 12:00:00 AM
Firstpage
404
Lastpage
408
Abstract
Previous tests on the breakdown of glass with direct potentials indicated the existence of three different regions of breakdown. The present paper describes similar tests on alternating potentials. The following conclusions are reached: 1. Three distinct regions of breakdown are obtained on alternating current as well as on direct current. 2. In the disruptive and intermediate regions, breakdown occurs at an alternating peak voltage approximately equal to the direct breakdown voltage. 3. In the thermal region, breakdown occurs at an alternating peak voltage somewhat lower than the direct breakdown voltage.
Keywords
Breakdown voltage; Electric breakdown; Glass; Solids; Temperature measurement; Voltage transformers;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1932.5056084
Filename
5056084
Link To Document