Title :
Forced extinction characteristics of secondary arc on UHV (1000 kV class) transmission lines
Author :
Goda, Yutaka ; Matsuda, Shoji ; Inaba, Tsuginori ; Ozaki, Yuzo
Author_Institution :
Central Res. Inst. of Electric Power Ind., Kanagawa, Japan
fDate :
7/1/1993 12:00:00 AM
Abstract :
Secondary arc extinction characteristics on ultrahigh voltage (UHV) (1000 kV) transmission lines by high-speed grounding switches (HSGSs) were investigated using the high-power test facilities of the Central Research Institute of Electric Power Industry (CRIEPI). The extinction time of secondary arcs by HSGSs is compared with the auto-extinction time. The characteristics of arcs initiated in a large gap (6 m) are described.<>
Keywords :
circuit-breaking arcs; earthing; power system protection; power transmission lines; switchgear testing; 1000 kV; 6 m; UHV; characteristics; extinction time; forced extinction; gap; high-speed grounding switches; protection; secondary arc; test facilities; testing; transmission lines;
Journal_Title :
Power Delivery, IEEE Transactions on