DocumentCode
998646
Title
The performance of reduced magnetic field power lines: theory and measurements on an operating line
Author
Olsen, R.G. ; James, D.C. ; Chartier, V.L.
Author_Institution
Sch. of Electr. Eng. & Comput. Sci., Washington State Univ., Pullman, WA, USA
Volume
8
Issue
3
fYear
1993
fDate
7/1/1993 12:00:00 AM
Firstpage
1430
Lastpage
1442
Abstract
Power engineers have been trying to find transmission line geometries that will reduce fields. One of the reduced field geometries is the double circuit, low reactance line. The results of a measurement and a theoretical program to study the magnetic field performance of such a double circuit 230 kV line with only one circuit energized and with both circuits paralleled in a low reactance configuration are presented. The measurements show that the reduced field line is more sensitive to deviations from balanced currents.<>
Keywords
electromagnetic fields; power transmission lines; 230 kV; EM fields; double circuit; geometries; magnetic field; performance; reactance; reduced magnetic field power lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.252670
Filename
252670